Semi-Hermetic Compressors Technical Details
 
 
4MM-20X - AWM
Cooling Capacity at Standard Condition 25,24kW
R134a, Evaporazione -10°C, Condensazione 45°C, Ritorno gas in aspirazione 20°C, Sottoraffreddamento 0K
 
Mechanical Data
Numero di cilindri4.0 Cilindrata , m3/h78.2
Alesaggio/Corsa, mm71.5/56.0 Lunghezza/Larghezza, mm657/501
Altezza, mm452.0 Peso Netto, kg182.0
Aspiraz., inch2 1/8 Mandata, inch.1 1/8
Quantità olio, l3.3 Foratura per staffaggio, mm381 x 305 (18.0)
PS Lato Alta, bar(g)28.0 Pressione sonora @ 1m (MT), dBA69.0
PS Lato Bassa, bar(g)22.5 Potenza sonora (MT), dBA80.0
 
Electrical Data
Max Corrente di Esercizio, A39.0 Corrente Rot. Blocc., A175.0
Classe involucro standardIP 54 (IEC 34)  
 
Related Documentation
Brochures
Refrigerant Transition Under F-gas Regulation 517/2014
 
Catalogue
Catalogo Prodotti 2016
 
Product leaflets
Stream Series
CoreSense™ Diagnostics for Refrigeration
Variable Speed Drives and Stream Compressors
Sound Shell for Copeland™ Compressors
Copeland Scroll And Stream Semi-Hermetic With Refrigerant R407F
 
Bollettino Tecnico
Motors for Copeland™ Semi-hermetic Compressors
CoreSense™ Diagnostics Module for Copeland Stream compressors
Modulo CoreSense™ Diagnostics - Guida Rapida d'Installazione
Refrigerant changeover - HFC R404A to HFC R407F/F, R448A, R449A
Digital Conversion kit - Quick installation guide
Sound shell for Copeland™ Stream compressors
Sound Shell per i Compressori Copeland™ Stream - Istruzioni Installazione
Use of Inverters with Stream Compressors
Unloaded Start for Semi-hermetic Compressors
Demand Cooling™ for Copeland™ Stream compressors with Demand Cooling Driver XEV01D
CoreSense Modbus Specifications
Stream Semi-hermetic Compressor Capacity Control
Refrigerants / Lubricants approved with Copeland™ Compressors
 
Guide all'Applicazione
Copeland Stream Semi-Hermetic Compressors - 4MF-13X to 4MK-35X & 6MM-30X to 6MK-50X
 
Certificati
Semi Stream 4M-6M: Conformity Declaration according to the RoHS Directive 2011/65/EU
Stream Semi-Hermetic Declaration of Incorporation according to the MD 2006/42/EC
Stream Semi-Hermetic Conformity of Declaration CE according to the Low Voltage Directive 2006/95/EC
 
Schema Elettrico
Wiring diagram for Stream Compressors AW...
Wiring Diagram for Stream Compressors EW...
 
Related Condensing Unit(s)
W9-4MM-20X    
 
 
 
 
 
Share