Semi-Hermetic Compressors Technical Details
 
 
D6SU-4000-DTC - AWM
Cooling Capacity at Standard Condition 21,16kW
R22, Evaporazione -35°C, Condensazione 40°C, Ritorno gas in aspirazione 20°C, Sottoraffreddamento 0K
 
Mechanical Data
Numero di cilindri6.0 Cilindrata , m3/h151.8
Alesaggio/Corsa, mm80.6/57.0 Lunghezza/Larghezza, mm740/570
Altezza, mm539.0 Peso Netto, kg265.0
Peso Lordo, Kg281.0 Aspiraz., inch2 5/8
Mandata, inch.1 5/8 Quantità olio, l6.8
Gamma di Frequenze, Hz25 - 60 Foratura per staffaggio, mm381 x 305 (18.0)
PS Lato Alta, bar(g)28.0 PS Lato Bassa, bar(g)22.5
 
Electrical Data
Max Corrente di Esercizio, A66.8 Corrente Rot. Blocc., A304.0
Classe involucro standardIP 54 (IEC 34)  
 
Related Documentation
Catalogue
Semi-Hermetic Compressors Product Selection Catalogue (2009)
Catalogo Prodotti 2014
 
Product leaflets
S-Series Semi-Hermetic Compressors with DTC for Low Temperature Applications, R22
 
Bollettino Tecnico
Semi-hermetic compressors - additional fans
Oil pressure safety control
Motors for Copeland™ Semi-hermetic Compressors
Refrigerant changeover from HCFC to HFC refrigerants
Mounting parts for semi-hermetic compressors
Starting methods
DTC for Semi-Hermetic R22 LT
Semi-Hermetic Compressors Capacity Control
Use of Inverters with DWM Copeland Semi-hermetic Compressors
Refrigerant Changeover from HCFC R22 to HFC R422AD
Oil additives
Model Designation for Copeland Brand Semi-Hermetic Compressor
Refrigerant changeover - HFC R404A to HFC R407F
Unloaded Start for Semi-hermetic Compressors
 
Guide all'Applicazione
DWM Copeland Semi-Hermetic Discus & Standard Compressors
 
Guide per sostituzioni
Replacement Guidelines for 2, 3, 4, 6 & 8 Cylinder S-Series and for 4 & 6 Cylinder Discus
Service Compressors for 4&6 Cylinder S-Series & Discus - D4D, D4S, D6D & D6S
 
Disegni Tecnici
Disegni per compressori D6SK e D6SU
 
Certificati
Semi Ref 4S / 6S / 8S / 6T: Declaration of Incorporation according to the Machinery Directive 2006/42/EC
Semi Ref 4S / 6S / 8S / 6T: Conformity Declaration CE 06 according to the Low Voltage Directive 2006/95/EC
Semi Ref 4S / 6S / 8S / 6T: Conformity Declaration according to the RoHS Directive 2011/65/EU
 
Schema Elettrico
Wiring diagram Semi Hermetics D4, D6, D8 AW*
Legend