XC1000D
XC1000D

Description

  • Controllers for compressor rack up to 15 compressors/fans
  • Up to: eight probe inputs
  • Up to: 15 configurable relays
  • Up to: 23 configurable d.i.
  • Two analogue outputs for frequency compressors
  • Two analogue outputs for inverter for fans
  • Proportional band or dead band control
  • Temperature and pressure display depending on the gas (Freon, NH3, CO2, ...)
  • Reduced set point for energy saving management
  • Hourly run time signals for maintenance
  • Dynamic set point for energy saving
  • Sub-cooling management
  • Standard communication protocol ModBUS-RTU
  • Hot key or Prog tool kit connector for a quick and easy programming

 XC1000D models can manage different compressor types:

  • scroll
  • semi-hermetic
  • multi stages
  • different power
  • screw (coming soon)

See Manual Download links at the bottom of this page

Models

 

 CONTROLLERS FOR COMPRESSOR RACK UP TO 15 COMPRESSORS/FANS

 
XC1008D 
CONTROLLER FOR MANAGING UP TO 8 COMPRESSORS OR FANS
D: DIN Rail

Generals
Power supply:
24Vac/dc

Probe inputs
Suction 1:
4÷20mA/0÷5V/PTC/NTC
Condensing 1: 4÷20mA/0÷5V/PTC/NTC
Auxiliary 1: PTC/NTC
Auxiliary 2: PTC/NTC

Digital inputs (main voltage)
Low pressure switch 1:
present
High pressure switch 1: present
Loads safety: 8

Digital inputs (line voltage)
N° 4:
configurable

Relay outputs
Loads:
8x7A configurabili
Alarms: 2x8A

Analog outputs
For frequency compressor:
4÷20mA/0÷10V optional
For inverter for fan: 4÷20mA/0÷10V optional

Other
Hot Key / Prog Tool Kit output:
present
Visograph output: VGC810
Serial output: RS485
External module connections: LAN optional

XC1011D

 
CONTROLLER FOR MANAGING UP TO 11 COMPRESSORS OR FANS
D: DIN Rail

Generals
Power supply: 24Vac/dc

Probe inputs
Suction 1:
4÷20mA/0÷5V/PTC/NTC
Suction 2: 4÷20mA/0÷5V/PTC/NTC
Condensing 1: 4÷20mA/0÷5V/PTC/NTC
Condensing 2: 4÷20mA/0÷5V/PTC/NTC
Auxiliary 1: PTC/NTC
Auxiliary 2: PTC/NTC
Auxiliary 3: PTC/NTC
Auxiliary 4: PTC/NTC

Digital inputs (main voltage)
Low pressure switch 1:
present
Low pressure switch 2: present
High pressure switch 1: present
High pressure switch 2: present
Loads safety: 11

Digital inputs (line voltage)
N° 4:
configurable

Relay outputs
Loads:
11x7A configurable
Alarms: 2x8A

Analog outputs
For frequency compressor:
2x4÷20mA/0÷10V optional
For inverter for fan: 2x4÷20mA/0÷10V optional

Other
Hot Key / Prog Tool Kit output:
present
Visograph output: VGC810
Serial output: RS485
External module connections: LAN optional


XC1015D

 
CONTROLLER FOR MANAGING UP TO 15 COMPRESSORS OR FANS
D: DIN Rail

Generals
Power supply:
24Vac/dc

Probe inputs
Suction 1:
4÷20mA/0÷5V/PTC/NTC
Suction 2: 4÷20mA/0÷5V/PTC/NTC
Condensing 1: 4÷20mA/0÷5V/PTC/NTC
Condensing 2: 4÷20mA/0÷5V/PTC/NTC
Auxiliary 1: PTC/NTC
Auxiliary 2: PTC/NTC
Auxiliary 3: PTC/NTC
Auxiliary 4: PTC/NTC

Digital inputs (main voltage)
Low pressure switch 1:
present
Low pressure switch 2: present
High pressure switch 1: present
High pressure switch 2: present
Loads safety: 15

Digital inputs (line voltage)
N° 4:
configurable

Relay outputs
Loads:
15x7A configurable
Alarms: 2x8A

Analog outputs
For frequency compressor:
2x4÷20mA/0÷10V optional
For inverter for fan: 2x4÷20mA/0÷10V optional

Other
Hot Key / Prog Tool Kit output:
present
Visograph output: VGC810
Serial output: RS485
External module connections: LAN optional


 

 PROGRAMMABLE GRAPHIC DISPLAY

 
VGC810 
PROGRAMMABLE GRAPHIC DISPLAY FOR XC1000D MODELS

82x156mm

Generals
Case: frontal 82x156mm; depth 24,7mm for panel mounting and 25,6mm for wall mounting
Front protection: IP65
Power supply: from controller (max distance: 100m)
VISOKEY output: present
Buzzer: optional

Manual Download

On this page we offer you to view or download existing documentation and print them at your desk.

model name click on the flag of your desired document language
XC1000D r.1.5A                   

Know more about XC1000D

Go to Top