EazyCool Technical Details
 
 
OMQ-45D - TFD
Cooling Capacity at Standard Condition 9.43kW
R404A, Evaporating -10°C, Ambient 32°C, Suction Gas Return 20°C, Subcooling 0K (Dew Point data)
 
Mechanical Data
Condenser/Fan TypeOCU9 6P/145 Number of Fans1.0
Total Fan Power Input, Watts145.0 Depth/Width, mm642/1250
Height, mm720.0 Gross Weight, kg146.0
Net Weight, kg118.0 Receiver Capacity, l8.1
Liquid Line, inch1/2 Air Flow, cu.m/sec1.0
High Side PS, bar(g)28.8 Low Side PS, bar(g)21.0
Suction TypeCu Tube Suction Diameter, inch7/8
Base mounting (hole dia), mm680 x 580 (12) Sound Pressure @ 10m, dBA39.0
 
Electrical Data
Condenser Fan Current for 1 fan (single phase)0.67 / 0.9 Compressor Maximum Operating Current, A12.3
Compressor Locked Rotor Current, A74.0  
 
Accessoires
Main Isolator Switch20A
Main Isolator Switch20A
Crankcase Heater70W External
Crankcase Heater70W External
Compressor contactorABB A16-30-01
Compressor contactorABB A16-30-01
Liquid sight glassALCO AMI-1SS4-1/2S
Liquid sight glassALCO AMI-1SS4-1/2S
Liquid solenoid valveALCO 200RBT4 fitted
Liquid solenoid valveALCO 200RBT4 fitted
Liquid solenoid valveALCO 200RBT4 shipped loose
Liquid solenoid valveALCO 200RBT4 shipped loose
Oil separatorALCO OSH-405
Oil separatorALCO OSH-405
HP/LP SwitchALCO PS2-W7A
HP/LP SwitchALCO PS2-W7A
Control circuit fuseS7-904-5355-0
Control circuit fuseS7-904-5355-0
Internal Suction LineInsulated
Internal Suction LineInsulated
Sound attenuationCompressor blanket
Sound attenuationCompressor blanket
Filter DrierALCO ADK Plus
Filter DrierALCO ADK Plus
Electronic controlerALCO EC2 551
Electronic controlerALCO EC2 551
Fan speed controlALCO FSX42S
Fan speed controlALCO FSX42S
 
Related Documentation
Brochures
Refrigerant Transition Under F-gas Regulation 517/2014
 
Catalogue
Copeland EazyCool™: Outdoor Scroll Condensing Units
General Product Catalogue 2017
 
Technical Information
Fans for Condensing Units
Oil additives
 
Application Guidelines
Copeland EazyCool™ Outdoor Condensing Units
Condensing Unit Controller EC2-5XX for Copeland EazyCool Outdoor Condensing Units
 
Old declarations (before April 2016)
OCU OM: Declaration of Incorporation according to the Machinery Directive 2006/42/EC
OCU OM: Conformity Declaration CE 06 according to the Low Voltage Directive 2006/95/EC
OCU OM: Conformity Declaration according to the RoHS Directive 2011/65/EU
 
Wiring Diagramms
Wiring diagram Outdoor Condensing Units OMQ 30D, OMQ 45D TFD
Legend
 
Declarations (after April 2016)
EU Declaration of Incorporation according to the Machinery Directive 2006/42/EC for Eazycool small outdoor Units
 
Related Compressor
ZBD45KCE   
 
 
 
Share