EazyCool Technical Details
OM-15 - PFJ
Cooling Capacity at Standard Condition 3.65kW
R404A, Evaporating -10°C, Ambient 32°C, Suction Gas Return 20°C, Subcooling 0K (Dew Point data)
Mechanical Data
Condenser/Fan TypeOCU4/121 Number of Fans1.0
Total Fan Power Input, Watts110.0 Depth/Width, mm630/1050
Height, mm720.0 Gross Weight, kg102.0
Net Weight, kg74.0 Receiver Capacity, l3.9
Liquid Line, inch1/2 Air Flow, cu.m/sec0.6
High Side PS, bar(g)28.8 Low Side PS, bar(g)21.0
Suction TypeCu Tube Suction Diameter, inch7/8
Base mounting (hole dia), mm480 x 580 (12) Sound Pressure @ 10m, dBA43.0
Electrical Data
Condenser Fan Current for 1 fan (single phase)0.45 / 0.65 Compressor Maximum Operating Current, A12.8
Compressor Locked Rotor Current, A58.0  
Crankcase Heater70W External
Liquid sight glassALCO AMI-1SS4-1/2S
Liquid solenoid valveALCO 200RBT4 fitted
Compressor contactorABB A16-30-01
Control circuit fuseS7-904-5355-0
Internal Suction LineInsulated
Fan speed controlALCO FSX42S
Oil separatorALCO OSH-405
Main Isolator Switch20A
Liquid solenoid valveALCO 200RBT4 shipped loose
Related Documentation
Refrigerant Transition Under F-gas Regulation 517/2014
Copeland EazyCool™: Outdoor Scroll Condensing Units
General Product Catalogue 2016
Technical Information
Fans for Condensing Units
Oil additives
Application Guidelines
Copeland EazyCool™ Outdoor Condensing Units
Old declarations (before April 2016)
OCU OM: Declaration of Incorporation according to the Machinery Directive 2006/42/EC
OCU OM: Conformity Declaration CE 06 according to the Low Voltage Directive 2006/95/EC
OCU OM: Conformity Declaration according to the RoHS Directive 2011/65/EU
Wiring Diagramms
Wiring diagram Outdoor Condensing Units PFJ
Declarations (after April 2016)
EU Declaration of Incorporation according to the Machinery Directive 2006/42/EC for Eazycool small outdoor Units
Related Compressor