EazyCool Technical Details
Cooling Capacity at Standard Condition 14.64kW
R404A, Evaporating -35°C, Ambient 32°C, Suction Gas Return 20°C, Subcooling 0K (Dew Point data)
Mechanical Data
Condenser/Fan TypeV6 6P/301 Number of Fans2.0
Total Fan Power Input, Watts550.0 Depth/Width, mm670/2100
Height, mm950.0 Gross Weight, kg303.0
Net Weight, kg259.0 Receiver Capacity, l24.0
Liquid Line, inch5/8 Air Flow, cu.m/sec1.8
High Side PS, bar(g)26.2 Low Side PS, bar(g)21.0
Suction TypeCu Tube Suction Diameter, inch1 3/8
Base mounting (hole dia), mm1330 x 620 (12) Oil reservoir capacity, l8.0
Electrical Data
Condenser Fan Current for 1 fan (single phase)1.3 / 1.6 Compressor Maximum Operating Current, A30.6
Compressor Locked Rotor Current, A198.0  
Crankcase Heater70W External
Fan speed controlALCO FSP150
Control circuit fuseS7-904-5355-0
Internal Suction LineInsulated
Liquid SubcoolerPlate Heat Exchanger
Oil separatorALCO OSH-407
LP SwitchALCO PS1 W3A (Automatic reset)
HP SwitchALCO PS3 WF4 (Automatic reset)
Liquid sight glassALCO AMI-1SS5-5/8S
Liquid solenoid valveALCO 200RBT5 fitted
Liquid solenoid valveALCO 200RBT5 shipped loose
Compressor contactorABB A26-30-01
Sound attenuationCompressor blanket
Main Isolator Switch32A
Filter DrierALCO ADK Plus
Vapour InjectionExpansion Valve
Electronic controlerALCO EC2 551
Oil Control SystemALCO Trax-Oil OM3
Related Documentation
Network Condensing Units with Digital Modulation
Copeland EazyCool™: Outdoor Scroll Condensing Units
General Product Catalogue 2015
Technical Information
Oil additives
Application Guidelines
Condensing Unit Controller EC2-5XX for Copeland EazyCool Outdoor Condensing Units
Outdoor Condensing Units for Refrigeration Networks
OCU Network: Declaration of Incorporation according to the Machinery Directive 2006/42/EC
OCU Network: Conformity Declaration CE 06 according to the Low Voltage Directive 2006/95/EC
OCU Network: Conformity Declaration according to the RoHS Directive 2011/65/EU
Wiring Diagramms
Related Compressor