Cooling Capacity at Standard Condition 14.27kW
R22, Evaporating -10°C, Ambient 32°C, Superheat 10K, Subcooling 0K
Mechanical Data
Condenser/Fan TypeV9 6P/145 Number of Fans2.0
Total Fan Power Input, Watts290.0 Depth/Width, mm670/2100
Height, mm950.0 Gross Weight, kg255.0
Net Weight, kg211.0 Liquid Line, inch5/8
Air Flow, cu.m/sec1.8 High Side PS, bar(g)26.2
Low Side PS, bar(g)21.0 Suction TypeCu Tube
Suction Diameter, inch1 3/8 Base mounting (hole dia), mm1330 x 620 (12)
Sound Pressure @ 10m, dBA46.0 Oil reservoir capacity, l8.0
Oil distribution linesSchreader connection  
Electrical Data
Condenser Fan Current for 1 fan (single phase)0.67 / 0.9 Compressor Maximum Operating Current, A2 x 12.80
Compressor Locked Rotor Current, A2 x 65.5  
Compressor contactorABB A16-30-01
Fan speed controlALCO FSP150
Control circuit fuseS7-904-5355-0
Internal Suction LineInsulated
Crankcase Heater2 x 70W External
Oil separatorALCO OSH-407
LP SwitchALCO PS1 W3A (Automatic reset)
HP SwitchALCO PS3 WF4 (Automatic reset)
Sound attenuationCompressor blanket
Main Isolator Switch32A
Liquid receiver unit, l90
Electronic controlerALCO EC2 551
Oil Control SystemALCO Trax-Oil OM3
Related Documentation
Copeland EazyCool™: Outdoor Scroll Condensing Units
General Product Catalogue 2015
Technical Information
Fans for Condensing Units
Oil additives
Application Guidelines
Condensing Unit Controller EC2-5XX for Copeland EazyCool Outdoor Condensing Units
Outdoor Condensing Units for Refrigeration Networks
OCU Network: Declaration of Incorporation according to the Machinery Directive 2006/42/EC
OCU Network: Conformity Declaration CE 06 according to the Low Voltage Directive 2006/95/EC
OCU Network: Conformity Declaration according to the RoHS Directive 2011/65/EU
Wiring Diagramms
Wiring diagram Network Condensing Unit OMTQ, OLTQ - TF
Related Compressor