EazyCool Technical Details
Cooling Capacity at Standard Condition 12.09kW
R404A, Evaporating -35°C, Ambient 32°C, Suction Gas Return 20°C, Subcooling 0K (Dew Point data)
Mechanical Data
Condenser/Fan TypeV6 6P/301 Number of Fans2.0
Total Fan Power Input, Watts550.0 Depth/Width, mm670/2100
Height, mm950.0 Gross Weight, kg258.0
Net Weight, kg214.0 Liquid Line, inch5/8
Air Flow, cu.m/sec1.8 High Side PS, bar(g)26.2
Low Side PS, bar(g)21.0 Suction TypeCu Tube
Suction Diameter, inch1 3/8 Base mounting (hole dia), mm1330 x 620 (12)
Sound Pressure @ 10m, dBA39.0 Liquid line from external, inch1 1/8
Electrical Data
Condenser Fan Current for 1 fan (single phase)1.3 / 1.6 Compressor Maximum Operating Current, A2 x 13.00
Compressor Locked Rotor Current, A2 x 74.0  
Fan speed controlALCO FSP150
Control circuit fuseS7-904-5355-0
Internal Suction LineInsulated
Liquid SubcoolerPlate Heat Exchanger
Crankcase Heater2 x 70W External
Oil separatorALCO OSH-407
LP SwitchALCO PS1 W3A (Automatic reset)
HP SwitchALCO PS3 WF4 (Automatic reset)
Compressor contactorABB A26-30-01
Sound attenuationCompressor blanket
Main Isolator Switch32A
Vapour InjectionExpansion Valve
Electronic controlerALCO EC2 551
Oil Control SystemALCO Trax-Oil OM3
Related Documentation
Network Condensing Units with Digital Modulation
Copeland EazyCool™: Outdoor Scroll Condensing Units
General Product Catalogue 2015
Technical Information
Oil additives
Application Guidelines
Condensing Unit Controller EC2-5XX for Copeland EazyCool Outdoor Condensing Units
Outdoor Condensing Units for Refrigeration Networks
OCU Network: Declaration of Incorporation according to the Machinery Directive 2006/42/EC
OCU Network: Conformity Declaration CE 06 according to the Low Voltage Directive 2006/95/EC
OCU Network: Conformity Declaration according to the RoHS Directive 2011/65/EU
Wiring Diagramms
Wiring diagram Network Condensing Unit OMTQ, OLTQ - TF
Related Compressor