EazyCool Technical Details
 
 
OMQ-92 - TWD
Cooling Capacity at Standard Condition 20.51kW
R404A, Evaporating -10°C, Ambient 32°C, Suction Gas Return 20°C, Subcooling 0K (Dew Point data)
 
Mechanical Data
Condenser/Fan TypeV6 6P/301 Number of Fans2.0
Total Fan Power Input, Watts550.0 Depth/Width, mm670/2100
Height, mm950.0 Gross Weight, kg281.0
Net Weight, kg246.0 Receiver Capacity, l17.7
Liquid Line, inch5/8 Air Flow, cu.m/sec1.8
High Side PS, bar(g)28.8 Low Side PS, bar(g)21.0
Suction TypeCu Tube Suction Diameter, inch1 3/8
Base mounting (hole dia), mm1330 x 620 (12) Sound Pressure @ 10m, dBA46.0
 
Electrical Data
Condenser Fan Current for 1 fan (single phase)1.3 / 1.6 Compressor Maximum Operating Current, A25.1
Compressor Locked Rotor Current, A167.0  
 
Accessoires
Crankcase Heater70W External
Oil separatorALCO OSH-407
HP/LP SwitchALCO PS2-W7A
Liquid sight glassALCO AMI-1SS5-5/8S
Liquid solenoid valveALCO 200RBT5 fitted
Liquid solenoid valveALCO 200RBT5 shipped loose
Compressor contactorABB A16-30-01
Internal Suction LineInsulated
Sound attenuationCompressor blanket
Filter DrierALCO ADK Plus
Fan speed controlALCO FSX42S
Main Isolator Switch32A
Filter DrierALCO ADK Plus
Main Isolator Switch32A
Fan speed controlALCO FSX42S
Liquid sight glassALCO AMI-1SS5-5/8S
HP/LP SwitchALCO PS2-W7A
Crankcase Heater70W External
Oil separatorALCO OSH-407
Compressor contactorABB A16-30-01
Liquid solenoid valveALCO 200RBT5 shipped loose
Liquid solenoid valveALCO 200RBT5 fitted
Internal Suction LineInsulated
Sound attenuationCompressor blanket
 
Related Documentation
Catalogue
Copeland EazyCool™: Outdoor Scroll Condensing Units
General Product Catalogue 2017
 
Technical Information
Fans for Condensing Units
Oil additives
 
Application Guidelines
Copeland EazyCool™ Outdoor Condensing Units
 
Old declarations (before April 2016)
OCU OM: Declaration of Incorporation according to the Machinery Directive 2006/42/EC
OCU OM: Conformity Declaration CE 06 according to the Low Voltage Directive 2006/95/EC
OCU OM: Conformity Declaration according to the RoHS Directive 2011/65/EU
 
Wiring Diagramms
Wiring diagram Outdoor Condensing Units OMQ, OLQ - TWD
Legend
 
Declarations (after April 2016)
EU Declaration of Incorporation according to the Machinery Directive 2006/42/EC for Eazycool large outdoor Units
 
Related Compressor
ZB92KCE   
 
 
 
Share