OM-26 - PFJ
Cooling Capacity at Standard Condition 4.53kW
R407C, Evaporating -10°C, Ambient 32°C, Superheat 10K, Subcooling 0K (Dew Point data)
Mechanical Data
Condenser/Fan TypeOCU6/271 Number of Fans1.0
Total Fan Power Input, Watts235.0 Depth/Width, mm630/1050
Height, mm720.0 Gross Weight, kg113.0
Net Weight, kg85.0 Receiver Capacity, l7.9
Liquid Line, inch1/2 Air Flow, cu.m/sec1.0
High Side PS, bar(g)28.8 Low Side PS, bar(g)21.0
Suction TypeCu Tube Suction Diameter, inch7/8
Base mounting (hole dia), mm480 x 580 (12) Sound Pressure @ 10m, dBA45.0
Electrical Data
Condenser Fan Current for 1 fan (single phase)1.15 / 1.4 Compressor Maximum Operating Current, A18.0
Compressor Locked Rotor Current, A97.0  
Crankcase Heater70W External
Liquid sight glassALCO AMI-1SS4-1/2S
Liquid solenoid valveALCO 200RBT4 fitted
Compressor contactorABB A16-30-01
Control circuit fuseS7-904-5355-0
Internal Suction LineInsulated
Single Phase EquipmentRelay, Start and Run Capacitor
Fan speed controlALCO FSX42S
Oil separatorALCO OSH-405
Main Isolator Switch20A
Liquid solenoid valveALCO 200RBT4 shipped loose
Filter DrierALCO ADK Plus
Related Documentation
General Product Catalogue 2015
Technical Information
Fans for Condensing Units
Oil additives
Application Guidelines
Copeland EazyCool™ Outdoor Condensing Units
OCU OM: Declaration of Incorporation according to the Machinery Directive 2006/42/EC
OCU OM: Conformity Declaration CE 06 according to the Low Voltage Directive 2006/95/EC
OCU OM: Conformity Declaration according to the RoHS Directive 2011/65/EU
Wiring Diagramms
Wiring diagram Outdoor Condensing Units PFJ
Related Compressor