Technical Details
 
 
V9-3SA-750 - EWL
Cooling Capacity at Standard Condition 24.88kW
R22, Evaporating 5°C, Ambient 32°C, Superheat 10K, Subcooling 0K
 
Mechanical Data
Condenser/Fan TypeV9/271 Number of Fans2.0
Total Fan Power Input, Watts470.0 Depth/Width, mm820/1330
Height, mm835.0 Gross Weight, kg295.0
Net Weight, kg215.0 Receiver Capacity, l18.9
Liquid Line, inch7/8 Air Flow, cu.m/sec2.2
High Side PS, bar(g)28.0 Low Side PS, bar(g)22.5
Suction TypeFixed Valve Suction Diameter, inch1 3/8
Base mounting (hole dia), mm1295 x 475 (14) Sound Pressure @ 10m, dBA54.5
 
Electrical Data
Condenser Fan Current for 1 fan (single phase)1.15 / 1.4 Compressor Maximum Operating Current, A18.5
Compressor Locked Rotor Current, A82.0  
 
Accessoires
Electrical box140W x 205H x 130D
Liquid Receiver23l instead of 18l
Crankcase Heater70W Internal
HP/LP SwitchALCO PS2-W7A
Oil Pressure SwitchOPS1
HousingV
Fan speed controlALCO FSX41S for R134a
Fan speed controlALCO FSX42S
 
Related Documentation
Catalogue
Semi-Hermetic Condensing Units
 
Technical Information
Fans for Condensing Units
Oil additives
 
Certificates
CU Semi 2S / 3S: Declaration of Incorporation according to the Machinery Directive 2006/42/EC
CU Semi 2S / 3S: Conformity Declaration CE 06 according to the Low Voltage Directive 2006/95/EC
CU Semi 2S / 3S: Conformity Declaration according to the RoHS Directive 2011/65/EU
 
Wiring Diagramms
Wiring diagram - Fan for Semi Hermetic Condensing Units
 
Related Compressor
D3SA-750