Technical Details
Technical Details
 
HLR13-ZBD76KCE - TFD
Cooling Capacity at Standard Condition 17.83kW
R404A, Evaporating -10°C, Condensing 45°C, Suction Gas Return 20°C, Subcooling 0K (Dew Point data)
 
Mechanical Data
Displacement @ 50 Hz, cu.m/h28.8 Length/Width, mm293/285
Height, mm533.0 Net Weight, kg61.7
Rotalock Suction, inch1 3/4 Rotalock Discharge, inch1 1/4
Oil Quantity, l3.3 Base mounting (hole dia), mm190 x 190 (8.5)
High Side PS, bar(g)32.0 Sound Pressure @ 1m (MT), dBA66.0
Low Side PS, bar(g)22.6 Low Side TS Max., °C50.0
Sound Power (MT), dBA77.0 Low Side TS Min., °C-35.0
Sound Power with Sound Shell (MT), dBA67.0  
 
Electrical Data
Maximum Operating Current, A20.4 Locked Rotor Current, A118.0
Default Enclosure ClassIP 21 (IEC 34)  
 
Accessoires
Mounting GrommetsStandard
Discharge Temperature ProtectionExternal Thermostat
Mounting GrommetsHard Mounts for Paralleling
Valve Coil220V
Valve Coil24V AC
Crankcase Heater90W External
Sound AttenuationSound Shell (10dBA)
Solenoid valveStandard
Digital Control KitEC2-552
Digital Control KitEC3-652
Oil Control SystemALCO Trax-Oil OM3
Digital DriverEC3-D13
 
Related Documentation
Catalogue
General Product Catalogue 2014
 
Product leaflets
Digital Receiver Unit HLR
 
Application Guidelines
Copeland Scroll DigitalTM Receiver Unit HLR
 
Technical Drawings
Drawing for HLR13 ZBD76
 
Certificates
OCU OM: Conformity Declaration according to the RoHS Directive 2011/65/EU
Conformity Declaration CE 06 according to the Low Voltage Directive 2006/95/EC
Declaration of Incorporation according to the Machinery Directive 2006/42/EC
 
Wiring Diagramms
HLR 13 Liquid receiver units
Legend