Technical Details
Technical Details
 
HLR31-ZBDT152KE - TFD
Cooling Capacity at Standard Condition 35.68kW
R404A, Evaporating -10°C, Condensing 45°C, Suction Gas Return 20°C, Subcooling 0K (Dew Point data)
 
Mechanical Data
Displacement @ 50 Hz, cu.m/h58.2 Length/Width, mm956/561
Height, mm945.0 Net Weight, kg182.0
Gross Weight, kg207.0 Stub Suction, inch1 5/8
Stub Discharge, inch1 3/8 Oil Quantity, l6.5
Base mounting (hole dia), mm600 x 280 (9.0) Sound Pressure @ 1m, dBA66.0
Sound Power, dBA77.0 Sound Power with Sound Shell, dBA67.0
High Side PS, bar(g)32.0 Low Side PS, bar(g)22.6
Low Side TS Max., °C50.0 Low Side TS Min., °C-35.0
 
Electrical Data
Maximum Operating Current, A2 x 20.40 Locked Rotor Current, A2 x 118.0
Winding Resistance, ohm1.2 Default Enclosure ClassIP 21 (IEC 34)
 
Accessoires
Digital Control KitEC2-552
HP/LP SwitchALCO PS3 & PS1
Crankcase Heater2 x 90W External
Oil separatorALCO OSH-411
 
 
 
 
 