Technical Details
Technical Details
 
HLR31-ZBDT60KCE - TFD
Cooling Capacity at Standard Condition 14.05kW
R404A, Evaporating -10°C, Condensing 45°C, Suction Gas Return 20°C, Subcooling 0K (Dew Point data)
 
Mechanical Data
Displacement @ 50 Hz, cu.m/h23.4 Length/Width, mm956/577
Height, mm917.0 Net Weight, kg122.8
Gross Weight, kg149.0 Stub Suction, inch1 3/8
Stub Discharge, inch7/8 Oil Quantity, l3.8
Base mounting (hole dia), mm600 x 280 (9.0) Sound Pressure @ 1m, dBA59.0
Sound Power, dBA70.0 High Side PS, bar(g)28.8
Low Side PS, bar(g)21.0  
 
Electrical Data
Maximum Operating Current, A7.90 + 10.30 Locked Rotor Current, A51.5 + 49.3
Winding Resistance, ohm3.6 Default Enclosure ClassIP 21 (IEC 34)
 
Accessoires
Digital Control KitEC2-552
HP/LP SwitchALCO PS3 & PS1
Crankcase Heater2 x 70W External
Oil separatorALCO OSH-407
 
 
 
 
 
Share