EazyCool Compact Technical Details
 
 
ZXME040E - TFD
Cooling Capacity at Standard Condition 6.99kW
R404A, Evaporating -10°C, Ambient 32°C, Suction Gas Return 20°C, Subcooling 0K (Dew Point data)
 
Mechanical Data
Condenser/Fan TypeZX040E/60 W Number of Fans1.0
Total Fan Power Input, Watts116.0 Depth/Width, mm1035/446
Height, mm840.0 Net Weight, kg91.0
Receiver Capacity, l4.1 Liquid Line, inch1/2
Air Flow, cu.m/sec0.8 High Side PS, bar(g)28.8
Low Side PS, bar(g)21.0 Suction TypeCu Tube
Suction Diameter, inch7/8 Base mounting (hole dia), mm580 x 388 (12)
Sound Pressure @ 10m, dBA40.0  
 
Electrical Data
Compressor Maximum Operating Current, A10.3 Compressor Locked Rotor Current, A49.3
 
Accessoires
Crankcase Heater70W External
Crankcase Heater70W External
Control circuit fuseS7-904-5355-0
Control circuit fuseS7-904-5355-0
Liquid InjectionDTC Valve
Liquid InjectionDTC Valve
LP SwitchALCO PS1 W3A (Automatic reset)
HP SwitchALCO PS3 WF4 (Automatic reset)
HP SwitchALCO PS3 WF4 (Automatic reset)
Filter DrierALCO ADK Plus
Filter DrierALCO ADK Plus
LP Adjustable Pressure SwitchAlco PS1-A3A
LP Adjustable Pressure SwitchAlco PS1-A3A
Liquid sight glassALCO MIA 012
Liquid sight glassALCO MIA 012
Circuit breaker, over current relay10 Amps
Circuit breaker, over current relay10 Amps
Compressor contactor18 Amps
Compressor contactor18 Amps
Electronic controlerEmerson XCM25D
 
Related Documentation
Brochures
Refrigerant Transition Under F-gas Regulation 517/2014
 
Catalogue
General Product Catalogue 2017
 
Product leaflets
Outdoor Refrigeration Unit - ZX Range
Copeland EazyCool™ ZX Condensing Units with ZX Cloud
 
Technical Information
Oil additives
XC645 Controller - Quick User's guide
ZX Cloud - Quick installation guide
Quick Installation and Troubleshooting Guide - ZX Units BOM 304 & 454
 
Application Guidelines
Copeland EazyCool™ Outdoor Condensing Units - ZX Range - BOM 302/452
Copeland EazyCool™ Outdoor Condensing Units - ZX Range - BOM 303/453
EazyCool™ Outdoor Condensing Unit - ZX Range BOM 304/454
 
Technical Drawings
Drawing for ZXME-040E-TFD, ZXLE-040E
 
Old declarations (before April 2016)
CU Scroll ZX: Conformity Declaration CE 06 according to the Low Voltage Directive 2006/95/EC
e
CU Scroll ZX: Declaration of Incorporation according to the Machinery Directive 2006/42/EC
 
Declarations (after April 2016)
EU Declaration of Incorporation according to the Machinery Directive 2006/42/EC for ZX Units
EU Declaration of Conformity according to the LVD 2014/35/EU, PED 2014/68/EU, EMC 2014/30/EU and RoHS 2011/65/EU for ZX Units
 
Related Compressor
ZX30KCE   
 
 
 
 
 
Share