Semi-Hermetic Compressors Technical Details
 
 
V9-2SK-65X
Cooling Capacity at Standard Condition 15.62kW
R404A, Evaporating -10°C, Ambient 32°C, Suction Gas Return 20°C, Subcooling 0K (Dew Point data)
 
Mechanical Data
Condenser/Fan TypeV9/271 Number of Fans2.0
Total Fan Power Input, Watts470.0 Depth/Width, mm820/1330
Height, mm835.0 Gross Weight, kg167.0
Net Weight, kg150.0 Receiver Capacity, l18.9
Liquid Line, inch7/8 Air Flow, cu.m/sec2.2
High Side PS, bar(g)31.0 Low Side PS, bar(g)22.5
Suction TypeFixed Valve Suction Diameter, inch1 1/8
Base mounting (hole dia), mm1295 x 475 (14) Sound Pressure @ 10m, dBA54.0
 
Electrical Data
Condenser Fan Current for 1 fan (single phase)1.15 / 1.4 Compressor Maximum Operating Current, A16.4
Compressor Locked Rotor Current, A85.3  
 
Accessoires
Electrical box140W x 205H x 130D
Electrical box140W x 205H x 130D
Electrical box140W x 205H x 130D
Electrical box140W x 205H x 130D
Liquid Receiver18l instead of 14l
Liquid Receiver18l instead of 14l
Liquid Receiver18l instead of 14l
Liquid Receiver18l instead of 14l
Crankcase Heater70W Internal
Crankcase Heater70W Internal
Crankcase Heater70W Internal
Crankcase Heater70W Internal
HP/LP SwitchALCO PS2-W7A
HP/LP SwitchALCO PS2-W7A
HP/LP SwitchALCO PS2-W7A
HP/LP SwitchALCO PS2-W7A
Oil Pressure SwitchOPS1
Oil Pressure SwitchOPS1
HousingV
HousingV
HousingV
HousingV
Fan speed controlALCO FSX42S
Fan speed controlALCO FSX42S
Fan speed controlALCO FSX42S
Fan speed controlALCO FSX42S
Oil Pressure SwitchOPS2 Sensor
Oil Pressure SwitchOPS2 Sensor
 
Related Documentation
Catalogue
Semi-Hermetic Condensing Units
 
Technical Information
Fans for Condensing Units
Oil additives
 
Old declarations (before April 2016)
CU Semi 2S / 3S: Declaration of Incorporation according to the Machinery Directive 2006/42/EC
CU Semi 2S / 3S: Conformity Declaration CE 06 according to the Low Voltage Directive 2006/95/EC
CU Semi 2S / 3S: Conformity Declaration according to the RoHS Directive 2011/65/EU
 
Wiring Diagramms
Wiring diagram - Fan for Semi Hermetic Condensing Units
 
Declarations (after April 2016)
EU Declaration of Incorporation according to the Machinery Directive 2006/42EC for Semi-Hermetics Units
 
Related Compressor
D2SK-65X   
 
 
 
 
 
Share