Semi-Hermetic Compressors Technical Details
 
 
B8-KJ-100
Cooling Capacity at Standard Condition 2.34kW
R22, Evaporating -10°C, Ambient 32°C, Suction Gas Return 20°C, Subcooling 0K
 
Mechanical Data
Condenser/Fan TypeB8/71 Number of Fans1.0
Total Fan Power Input, Watts85.0 Depth/Width, mm570/560
Height, mm396.0 Gross Weight, kg67.5
Net Weight, kg57.5 Receiver Capacity, l3.3
Liquid Line, inch1/2 Air Flow, cu.m/sec0.4
High Side PS, bar(g)31.0 Low Side PS, bar(g)22.5
Suction TypeFixed Valve Suction Diameter, inch5/8
Base mounting (hole dia), mm530 x 330 (11) Sound Pressure @ 10m, dBA39.0
 
Electrical Data
Condenser Fan Current for 1 fan (single phase)0.38 / 0.45 Compressor Maximum Operating Current, A2.7
Compressor Locked Rotor Current, A15.5  
 
Accessoires
HP/LP SwitchALCO PS2-W7A
Crankcase Heater27W Internal
Fan speed controlALCO FSX41S for R134a
Fan speed controlALCO FSX42S
HousingBD
Crankcase Heater27W Internal
HousingBD
HP/LP SwitchALCO PS2-W7A
Fan speed controlALCO FSM42S
Fan speed controlALCO FSM41S for R134a
 
Related Documentation
Catalogue
Semi-Hermetic Condensing Units
 
Technical Information
Fans for Condensing Units
Oil additives
 
Technical Drawings
Drawing for Unit B8-K ...
 
Old declarations (before April 2016)
CU Semi DK / DL: Declaration of Incorporation according to the Machinery Directive 2006/42/EC
CU Semi DK / DL: Conformity Declaration CE 06 according to the Low Voltage Directive 2006/95/EC
CU Semi DK / DL: Conformity Declaration according to the RoHS Directive 2011/65/EU
 
Wiring Diagramms
Wiring diagram - Fan for Semi Hermetic Condensing Units
 
Declarations (after April 2016)
EU Declaration of Incorporation according to the Machinery Directive 2006/42EC for Semi-Hermetics Units
 
Related Compressor
KJ-100   KJ-100   
 
 
 
 
 
Share