Semi-Hermetic Compressors Technical Details
 
 
4MT-22X - AWM
Cooling Capacity at Standard Condition 28.71kW
R134a, Evaporating -10°C, Condensing 45°C, Suction Gas Return 20°C, Subcooling 0K
 
Mechanical Data
Number of cylinders4.0 Displacement @ 50 Hz, cu.m/h87.7
Bore/Stroke, mm75.7/56.0 Length/Width, mm657/501
Height, mm452.0 Net Weight, kg183.0
Suction, inch2 1/8 Discharge, inch1 3/8
Oil Quantity, l3.3 Base mounting (hole dia), mm381 x 305 (18.0)
High Side PS, bar(g)28.0 Sound Pressure @ 1m (MT), dBA70.0
Low Side PS, bar(g)22.5 Sound Power (MT), dBA81.0
 
Electrical Data
Maximum Operating Current, A44.5 Locked Rotor Current, A175.0
Default Enclosure ClassIP 54 (IEC 34)  
 
Related Documentation
Brochures
Stream - The-state-of-the-art semi-hermetic piston technology
Refrigerant Transition Under F-gas Regulation 517/2014
 
Catalogue
General Product Catalogue 2016
 
Product leaflets
Stream Series
CoreSense™ Diagnostics for Refrigeration
Variable Speed Drives and Stream Compressors
Sound Shell for Copeland™ Compressors
Copeland Scroll And Stream Semi-Hermetic With Refrigerant R407F
 
Technical Information
Motors for Copeland™ Semi-hermetic Compressors
CoreSense™ Diagnostics Module for Copeland Stream compressors
CoreSense™ Diagnostics Module - Quick installation guide
Refrigerant changeover - HFC R404A to HFC R407F/F, R448A, R449A
Digital Conversion kit - Quick installation guide
Sound shell for Copeland™ Stream compressors
Sound shell for Copeland™ Stream compressors - Quick installation guide
Use of Inverters with Stream Compressors
Unloaded Start for Semi-hermetic Compressors
Demand Cooling™ for Copeland™ Stream compressors with Demand Cooling Driver XEV01D
CoreSense™ Diagnostics for Stream compressors
CoreSense Modbus Specifications
Stream Semi-hermetic Compressor Capacity Control
Refrigerants / Lubricants approved with Copeland™ Compressors
 
Application Guidelines
Copeland Stream Semi-Hermetic Compressors - 4MF-13X to 4MK-35X & 6MM-30X to 6MK-50X
 
Old declarations (before April 2016)
Semi Stream 4M-6M: Conformity Declaration according to the RoHS Directive 2011/65/EU
Stream Semi-Hermetic Declaration of Incorporation according to the MD 2006/42/EC
Stream Semi-Hermetic Conformity of Declaration CE according to the Low Voltage Directive 2006/95/EC
 
Wiring Diagramms
Wiring diagram for Stream Compressors AW...
Wiring Diagram for Stream Compressors EW...
 
Declarations (after April 2016)
EU Declaration of Conformity according to the LVD 2014/35/EU and RoHS 2011/65/EU for Semi Copeland Black and Stream
 
Related Condensing Unit(s)
W9-4MT-22X    
 
 
 
 
 
Share