Semi-Hermetic Compressors Technical Details
 
 
6MI-40X - AWM
Cooling Capacity at Standard Condition 0.0kW
No Standard Condition specified.
 
Mechanical Data
Number of cylinders6.0 Displacement @ 50 Hz, cu.m/h120.5
Bore/Stroke, mm71.5/57.5 Length/Width, mm695/547
Height, mm450.0 Net Weight, kg219.0
Suction, inch2 1/8 Discharge, inch1 3/8
Oil Quantity, l3.3 Base mounting (hole dia), mm381 x 305 (18.0)
High Side PS, bar(g)28.0 Sound Pressure @ 1m (MT), dBA72.0
Low Side PS, bar(g)22.5 Sound Power (MT), dBA83.0
 
Electrical Data
Maximum Operating Current, A71.4 Locked Rotor Current, A304.0
Default Enclosure ClassIP 54 (IEC 34)  
 
Accessoires
Mounting Springs4
Crankcase Heater100W Internal
Additional Cooling70W Vertical Air Flow Fan
Unloaded StartAvailable
Capacity ControlCapacity Steps 66/33%
Oil Pressure SwitchOPS2 Electronic Switch
Oil Pressure SwitchOPS2 Sensor
Enclosure ClassIP56
Deep Oil SumpMounted
Adapter KitFor Parallel Operation
Check Valve (NRV)For unloaded start operation
 
Related Documentation
Product leaflets
Stream Series
CoreSense Diagnostics for Refrigeration
 
Technical Information
Model Designation for Copeland Brand Semi-Hermetic Compressor
Refrigerant changeover - HFC R404A to HFC R407F
Digital Conversion kit - Quick installation guide
 
Certificates
Stream 4M, 6M: Conformity Declaration CE 06 according to the Low Voltage Directive 2006/95/EC
Stream 4M, 6M: Declaration of Incorporation according to the Machinery Directive 2006/42/EC
Semi Stream 4M-6M: Conformity Declaration according to the RoHS Directive 2011/65/EU
 
Wiring Diagramms
Wiring diagram for Stream Compressors AW...
Wiring Diagram for Stream Compressors EW...