Semi-Hermetic Compressors Technical Details
 
 
D6SF-200X - AWM
Cooling Capacity at Standard Condition 23.79kW
R134a, Evaporating -10°C, Condensing 45°C, Superheat 10K, Subcooling 0K
 
Mechanical Data
Number of cylinders6.0 Displacement @ 50 Hz, cu.m/h84.0
Bore/Stroke, mm63.5/50.8 Length/Width, mm740/540
Height, mm490.0 Net Weight, kg212.0
Gross Weight, kg228.0 Rotalock Discharge, inch1 3/8
Suction, inch2 1/8 Oil Quantity, l3.3
Frequency Range, Hz25 - 60 Base mounting (hole dia), mm381 x 305 (18.0)
High Side PS, bar(g)28.0 Low Side PS, bar(g)22.5
 
Electrical Data
Maximum Operating Current, A38.4 Locked Rotor Current, A175.0
Default Enclosure ClassIP 54 (IEC 34)  
 
Accessoires
Mounting Springs4
Crankcase Heater100W Internal
Additional Cooling70W Vertical Air Flow Fan
Unloaded StartAvailable
Capacity ControlCapacity Steps 66/33%
Discharge Temperature ProtectionHead PTC sensor
Oil Pressure SwitchOPS2 Electronic Switch
Oil Pressure SwitchOPS2 Sensor
Enclosure ClassIP56
Deep Oil SumpMounted
Adapter KitFor Parallel Operation
Check Valve (NRV)For unloaded start operation
InverterControl Techniques SK 4402
 
Related Documentation
Catalogue
General Product Catalogue 2014
 
Technical Information
Motors for Copeland® Semi-hermetic Compressors
Use of Inverters with DWM Copeland Semi-hermetic Compressors
Oil additives
Model Designation for Copeland Brand Semi-Hermetic Compressor
Refrigerant changeover - HFC R404A to HFC R407F
Unloaded Start for Semi-hermetic Compressors
 
Application Guidelines
DWM Copeland Semi-Hermetic Discus & Standard Compressors
 
Replacement Guidelines
Replacement Guidelines for 2, 3, 4, 6 & 8 Cylinder S-Series and for 4 & 6 Cylinder Discus
Service Compressors for 4&6 Cylinder S-Series & Discus - D4D, D4S, D6D & D6S
 
Technical Drawings
Drawing for compressor D6SA, D6SF, D6SL and D6SH200
 
Wiring Diagramms
Wiring diagram Semi Hermetics D4, D6, D8 AW*
Legend