D2DC-50X - AWM
Cooling Capacity at Standard Condition 0.0kW
No Standard Condition specified.
 
Mechanical Data
Number of cylinders2.0 Displacement @ 50 Hz, cu.m/h16.8
Bore/Stroke, mm63.6/30.5 Length/Width, mm590/330
Height, mm470.0 Net Weight, kg132.0
Gross Weight, kg141.0 Rotalock Discharge, inch7/8
Suction, inch1 3/8 Oil Quantity, l2.3
Frequency Range, Hz25 - 60 Base mounting (hole dia), mm295 x 279 (14.0)
Sound Pressure @ 1m, dBA65.0 High Side PS, bar(g)28.0
Low Side PS, bar(g)22.5  
 
Electrical Data
Maximum Operating Current, A9.0 Locked Rotor Current, A55.0
Default Enclosure ClassIP 54 (IEC 34)  
 
Accessoires
Mounting Springs4
Crankcase Heater70W Internal
Additional Cooling70W Vertical Air Flow Fan
Unloaded StartAvailable
Oil Pressure SwitchOPS2 Electronic Switch
Oil Pressure SwitchOPS2 Sensor
Enclosure ClassIP56
Deep Oil SumpMounted
Adapter KitFor Parallel Operation
Check Valve (NRV)For unloaded start operation
InverterControl Techniques SKB 3400750
 
Related Documentation
Catalogue
General Product Catalogue 2016
 
Technical Information
Motors for Copeland™ Semi-hermetic Compressors
Use of Inverters with DWM Copeland Semi-hermetic Compressors
Oil additives
Model Designation for Copeland Brand Semi-Hermetic Compressor
Unloaded Start for Semi-hermetic Compressors
DWM Copeland semi-hermetic compressors - Oil pressure differential switch OPS2
 
Application Guidelines
Semi-Hermetic Compressors - Discus, K, L & S-Series
 
Technical Drawings
Drawing for compressor D2D
 
Wiring Diagramms
Wiring diagram Semi Hermetics D2D, D3, D9 AW*
Legend
 
Declarations (after April 2016)
EU Declaration of Conformity according to the LVD 2014/35/EU and RoHS 2011/65/EU for Semi-Hermetics DWM
EU Declaration of Incorporation according to the Machinery Directive 2006/42/EC for Semi-Hermetics DWM
 
 
 
 
 
Share