LL-40X - EWL
Cooling Capacity at Standard Condition 0.0kW
No Standard Condition specified.
Mechanical Data
Number of cylinders2.0 Displacement @ 50 Hz, cu.m/h18.2
Bore/Stroke, mm60.4/36.5 Length/Width, mm470/330
Height, mm385.0 Net Weight, kg87.0
Gross Weight, kg93.0 Suction, inch1 1/8
Discharge, inch5/8 Oil Quantity, l2.0
Frequency Range, Hz25 - 60 Base mounting (hole dia), mm295 x 279 (14.0)
Sound Pressure @ 1m, dBA56.0 High Side PS, bar(g)28.0
Low Side PS, bar(g)22.5  
Electrical Data
Maximum Operating Current, A9.5 Locked Rotor Current, A68.5
Default Enclosure ClassIP 54 (IEC 34)  
Mounting Springs4
Additional Cooling1 or 2 ways water Coil
Additional Cooling25W Horizontal Air Flow Fan
Crankcase Heater70W Internal
Additional Cooling70W Vertical Air Flow Fan
Adapter KitFor Parallel Operation
InverterControl Techniques SKB 3400750
Related Documentation
Semi-Hermetic Compressors Product Selection Catalogue (2009)
General Product Catalogue 2015
Technical Information
Semi-hermetic compressors - additional fans
Motors for Copeland™ Semi-hermetic Compressors
Refrigerant changeover from HCFC to HFC refrigerants
Mounting parts for semi-hermetic compressors
Use of Inverters with DWM Copeland Semi-hermetic Compressors
Refrigerant Changeover from HCFC R22 to HFC R422AD
Oil additives
Model Designation for Copeland Brand Semi-Hermetic Compressor
Refrigerants / Lubricants approved with Copeland™ Compressors
Application Guidelines
Semi-Hermetic Compressors - Discus, K, L & S-Series
Replacement Guidelines
Technical Drawings
Drawing for compressor DL
Semi Ref DK / DL: Declaration of Incorporation according to the Machinery Directive 2006/42/EC
Semi Ref DK / DL: Conformity Declaration CE 06 according to the Low Voltage Directive 2006/95/EC
Semi Ref DK / DL: Conformity Declaration according to the RoHS Directive 2011/65/EU
Wiring Diagramms
Wiring diagram Semi Hermetics Compressors DK DL EW*
Related Condensing Unit(s)
H8-LL-40X    P8-LL-40X