Copeland Brand Products R 410A
Copeland Brand Products R 410A
If you don't find an answer to your question, please
contact us
so we can help you.
Click on the links below to view answers:
Can an R-22 system be switched to R-410A?
Generally not, although in the case of split systems, the outdoor unit can be replaced with an R-410A unit following the manufacturer's guidelines. Care must be taken that the indoor coil is rated for the required R-410A burst pressure. Because of the thermodynamic and pressure properties of R-410A, compressors were redesigned to properly match motors with displacement as well as meeting the higher shell burst pressure requirements. A compressor designed for R-22 would be overloaded and trip the motor protector if it were to pump R-410A at air conditioning conditions.
Where do I find more information on R-410A Copeland Scroll® compressors?
For more information on this topic see AE Bulletin 4-1301 and visit the air conditioning products page. Visit the R-410A Knowledge Site to view Emerson's research results on environmentally friendly refrigerants. If you do not find an answer to your question, please contact us so we can help you.
Do suction and discharge lines have to be resized with R-410A?
No, the same line sizes used for R-22 are used for R-410A. The ideal line size for R-410A is smaller in diameter than R-22 tubing and falls between the standard available nominal refrigerant tubing sizes. The same tubing sizes used for R-22 must be used for R-410A to avoid excessive pressure drops when using the next smaller tube.
Do suction and discharge lines have to be resized with R-410A?
No, the same line sizes used for R-22 are used for R-410A. The ideal line size for R-410A is smaller in diameter than R-22 tubing and falls between the standard available nominal refrigerant tubing sizes. The same tubing sizes used for R-22 must be used for R-410A to avoid excessive pressure drops when using the next smaller tube.
How can a Copeland® brand R-410A compressor be identified?
Currently only Emerson builds scroll compressors released for R-410A. If the second letter of the model number is a P, then the compressor is designated for R-410A. For example: ZP54K3E-XXX as opposed to the R-22 designation: ZR54KsE-XXX. Go to Online Product Information (OPI) for more information.
Since moisture is such a concern, what filter dryers can be used with R-410A?
A 100% molecular sieve drier should be used in any new system or system where no acid is present. Should non-organic acid be present, then a filter with 25% activated alumina may be installed. For more information on this topic see AE Bulletin 11-1297.
What oil is available? Should additional oil be needed in a system?
Emerson wholesalers carry Ultra 22CC POE oil that is compatible with the oil in the currently released R-410A product.
Besides the higher pressures, are there other concerns when working with and R-410A compressor?
Yes, moisture and contaminants:
* Moisture: Because Polyol Ester Oil (POE) absorbs moisture at a faster and higher rate than mineral oil, the time that the inside of the compressor can be exposed to the atmosphere is much shorter. Good practice dictates that the compressor plugs not be pulled until the compressor is set in place.
* System Contaminants: Polyol Ester Oil (POE) is an excellent cleaner and will carry copper-oxides and other contaminants, that mineral oil left in place, through the system, possibly clogging expansion devices. An inert gas, such as nitrogen, must be swept though the system to prevent copper-oxide formation during brazing.
* Both moisture and contaminant control should be normal procedures for R-22 installations and are even more important when installing a system with POE oil.
What are the major differences between an R-22 and R-410A compressor?
There are three distinct design differences between and R-22 and R-410A compressor:
* Different Oil: Because mineral oil, normally used in R-22 compressors, is not miscible with HFC refrigerants such as R-410A, Copeland uses a synthetic Polyol Ester Oil (POE) in R-410A approved compressors.
* Reduced Compressor Displacement: A pound of R-410A has approximately the same heat carrying capacity relationship to R-22 as R-22 has to R-12, therefore, the compressor displacement has to be reduced approximately 40% for a given motor horsepower. Using a compressor designed for R-22 to pump R-410A would overload the motor and cause protector trips.
* Higher Shell Burst Pressure Requirement: At any given saturated temperature, R-410A has approximately 60% higher pressure than R-22, which require compressor shells to meet this higher pressure requirement.