IC100 iCHILL
IC100 iCHILL

Description

IC100 is Dixell’s answer to real management and control requirements of chiller unit and heat pump single circuit (gas and water reversibility), with up two compressors or a single compressor with capacity stages, by means of a compact instrument, the possibility of controlling and managing system like: air / air – "roof top", air / water, water / water, motor-condensing, refrigeration dryers.

  • Single compressor stand-by
  • Forced defrosting
  • Combined defrosting
  • Twin compressor functioning
  • Open collector output polarity management
  • Unloading function
  • Alarm control, even in stand-by or remote off
  • Alarm reset password
  • 4÷20mA output for condensing management
  • NTC, 4÷20mA and 0÷5V ratiometric analogue input
  • Internal data logger (up to 50 alarm)
  • Real time clock
  • Energy saving
  • Easy programming through HOT KEY or PC (PROG TOOL KIT)
  • TTL (convertible in RS485) serial output with ModBUS protocol

See Manual Downoads links at the bottom of this page.

Models

 

 1 CIRCUIT AND 1 COMPRESSOR CONTROLLERS

 
IC100CX

ADVANCED MULTIFUNCTION CONTROLLER FOR CHILLER WITH 1 CIRCUIT AND 1 COMPRESSOR
CX: 32x74mm

Generals
N° digits display:
first: ± 4 d.p. second: ± 4 d.p.
Power supply: 12Vac/dc, 24Vac/dc optional

Probe inputs
Pb1:
NTC configurable
Pb2: NTC configurable
Pb3: NTC / 4÷20mA / 0,5V configurable
Pb4: NTC / digital input configurable
Digital inputs
High pressure:
present
Low pressure: present
N° 4: configurable

Relay outputs
RL1 Compressor 1:
* 8A
RL2: * 8A configurable
RL3: 8A configurable
RL4: * 8A configurable
RL5: * 8A configurable, optional

Other outputs
Analog output for fan speed module:
4÷20mA optional or 0÷10V optional
Signal output for triac or ON/OFF fan module: ° PWM
Open collector output: 12Vdc-40mA max
Remote keyboards: VICX610
Serial output: TTL
Hot Key / Prog Tool Kit output: present

Other
Triac module inside:
2A optional
RTC: optional
Buzzer: optional

* With triac module: RL1 = 5A - RL2 = 5A - RL4 = 5A config - RL5 = not present
° PWM output becames output configured for aux relay control, when the triac is incorporated

IC111CX

ADVANCED MULTIFUNCTION CONTROLLER FOR CHILLER/HEAT PUMP WITH 1 CIRCUIT AND 1 COMPRESSOR
CX: 32x74mm

Generals
N° digits display:
first: ± 4 d.p. second: ± 4 d.p.
Power supply: 12Vac/dc, 24Vac/dc optional

Probe inputs
Pb1:
NTC configurable
Pb2: NTC configurable
Pb3: NTC / 4÷20mA / 0,5V configurable
Pb4: NTC / digital input configurable

Digital inputs
High pressure:
present
Low pressure: present
N° 4: configurable

Relay outputs
RL1 Compressor 1:
* 8A
RL2: * 8A configurable
RL3: 8A configurable
RL4: * 8A configurable
RL5: * 8A configurable, optional

Other outputs
Analog output for fan speed module:
4÷20mA optional or 0÷10mA optional
Signal output for triac or ON/OFF fan module: ° PWM
Open collector output: 12Vdc-40mA max
Remote keyboards: VICX610
Serial output: TTL
Hot Key / Prog Tool Kit output: present

Other
Triac module inside:
2A optional
RTC: optional
Buzzer: optional
* With triac module: RL1 = 5A - RL2 = 5A - RL4 = 5A config - RL5 = not present
° PWM output becames output configured for aux relay control, when the triac is incorporated

 

 1 CIRCUIT AND 2 COMPRESSOR CONTROLLERS

 
IC120CX


ADVANCED MULTIFUNCTION CONTROLLER FOR CHILLER WITH 1 CIRCUIT AND 2 COMPRESSORS
CX: 32x74mm

Generals
N° digits display:
first: ± 4 d.p. second: ± 4 d.p.
Power supply: 12Vac/dc, 24Vac/dc optional

Probe inputs
Pb1: NTC configurable
Pb2: NTC configurable
Pb3: NTC / 4÷20mA / 0÷5V configurable
Pb4: NTC / digital input configurable

Digital inputs
High pressure:
present
Low pressure: present
N° 4: configurable

Relay outputs
RL1 Compressor 1:
8A
RL2: 8A configurable
RL3: 8A configurable
RL4: 8A configurable
RL5: 8A configurable

Other outputs
Analog output for fan speed module:
4÷20mA optional or 0÷10V optional
Signal output for triac or ON/OFF fan module: PWM
Open collector output: 12Vdc-40mA max
Remote keyboards: VICX610
Serial output: TTL
Hot Key / Prog Tool Kit output: present

Other
RTC:
optional
Buzzer: optional

IC121CX


ADVANCED MULTIFUNCTION CONTROLLER FOR CHILLER/HEAT PUMP WITH 1 CIRCUIT AND 2 COMPRESSORS
CX: 32x74mm

Generals
N° digits display: first:
± 4 d.p. second: ± 4 d.p.
Power supply: 12Vac/dc, 24Vac/dc optional

Probe inputs
Pb1:
NTC configurable
Pb2: NTC configurable
Pb3: NTC / 4÷20mA / 0÷5V configurable
Pb4: NTC / digital input configurable

Digital inputs
High pressure:
present
Low pressure: present
N° 4: configurable

Relay outputs
RL1 Compressor 1: 8A
RL2: 8A configurable
RL3: 8A configurable
RL4: 8A configurable
RL5: 8A configurable

Other outputs
Analog output for fan speed module:
4÷20mA optional or 0÷10mA optional
Signal output for triac or ON/OFF fan module: PWM
Open collector output: 12Vdc-40mA max
Remote keyboards: VICX610
Serial output: TTL
Hot Key / Prog Tool Kit output: present

Other
RTC:
optional
Buzzer: optional

 

 REMOTE KEYBOARDS FOR IC100 SERIES

 
VICX610


6 KEY KEYBOARD FOR IC100CX CONTROLLERS
VICX: 100x64mm

Generals
N° digits display:
first: ± 4 d.p. second: ± 4 d.p.
Power supply: from controller (max distance: 150m)
Internal NTC probe: optional
Buzzer: optional

 

Manual Download

On this page we offer you to view or download existing documentation and print them at your desk.

model name click on the flag of your dESired document language
 IC110CX             
 IC111CX             
 IC120CX                    
 IC121CX                

  Go to Top